DSE5220
Deep Sea Controller Auto Start Control Module DSE5220 for generator
Deep Sea Controller Auto Start Control Module DSE703 for generator
DSE703 Deep Sea legacy auto-start controller.
| Warranty | 13 months |
|---|---|
| Place of Origin | Fujian, China |
| Brand Name | KAIYUE |
| Model Number | DSE703 |
| OVERALL SIZE | 165 x 125 x 29 mm |
| PANEL CUTOUT SIZE | 149 x 109 mm |
| Certification | CE,ISO9001 |
| Parameter | Original | KAIYUE Replacement |
|---|---|---|
| Control type | AMF / MRS / Auto-Start | AMF mains-failure and remote start |
| DC supply | 12/24 VDC nominal | 12/24 VDC selectable; confirm battery system |
| AC sensing | 0–600 VAC, 1/3 phase | 0–600 VAC sensing; terminal map supplied |
| Output rating | Relay outputs, reference-dependent | Relay outputs sized for stated contactor/solenoid loads |
| Magnetic pickup input | 0.5–35 VAC, 10–10,000 Hz | 0.5–35 VAC compatible pickup input |
| Panel cut-out / dimensions | Reference drawing required | Proposed drawing confirmed before shipment |
| Weight / protection | Reference unit; IP rating by enclosure | Approx. 0.48 kg; front sealing option by project |
| Product Name | Deep Sea Controller Auto Start Control Module DSE703 for generator | |
| Output A (Fuel)MAINS (UTILITY) | Voltage Range | 15 V to 415 V AC (Ph to N)26 V to 719 V AC (Ph to Ph) |
| Frequency Range | 3.5 Hz to 75 Hz | |
| OUTPUTS | Output A (Fuel) | 10 A short term, 5 A continuous,at supply voltage |
| Output B (Start) | 10 A short term, 5 A continuous,at supply voltage | |
| Auxiliary Outputs C, D, E &F | 2 A DC at supply voltage | |
Offers explicitly identifying DSE703 ranged from US$39.04 to US$370.61 per module. The highest quote was an equipment-specific engine-control spare, whereas numerous standard replacement-panel offers were much lower. For rental-fleet or generator-service procurement, check whether the required unit needs equipment-specific wiring or configuration before comparing that premium with a generic module. Confirm the installed connections, operating logic and supplied accessories; used units and ambiguous bare '703' references are excluded.
Identify the installed model and compare terminal layout, functions and panel cut-out with the proposed replacement — confirm the specification with our team.
View this answer in FAQs ↗Some replacements are near drop-in while others require wiring and configuration changes. Confirm compatibility for the specific pair of models — confirm the specification with our team.
View this answer in FAQs ↗They are widely used for generator set control, including manual, automatic and AMF operation, with protection and monitoring functions — confirm the specification with our team.
View this answer in FAQs ↗Overcrank indicates the engine did not start within the configured crank attempts. Check fuel supply, starting system, speed sensing and crank timing settings.
View this answer in FAQs ↗Provide generator rating, engine type, required features, communication needs, panel space and photos of the existing installation. ---
View this answer in FAQs ↗