KAIYUE KAIYUEGENERATOR PARTS
Get a Quote
Generator AVR

SR7

Generator Automatic Voltage Regulator Mecc Alte AVR SR7

SR7 Mecc Alte AVR for legacy ECP alternators.

Model NumberSR7
Overall Size92×92×55mm
Weight0.4kg
Discuss on WhatsApp ↗

Technical Data

Warranty 13 months
Place of Origin Fujian, China
Brand Name KAIYUE
Model Number SR7
Certification CE,ISO9001
Overall Size 92×92×55mm
Weight 0.4kg
ParameterOriginalKAIYUE Replacement
Excitation typeSHUNT / PMG / AREP, model dependentAREP auxiliary-winding configuration
Voltage adjustmentTypically ±5% trimTypically ±5% trim with stable response
Frequency range40–70 Hz reference dependent40–70 Hz operating window; verify under-speed protection
Working temperatureReference datasheet-40 to +65 °C design target; confirm derating
Power consumptionReference datasheetLow-power regulator circuit; value confirmed with quotation
Voltage accuracyReference datasheetTypically within ±1% after commissioning
Terminal descriptionModel-specific terminalsSensing, field, power and droop terminals identified on drawing
Product Name Automatic Voltage Regulator AVR SR7
Sensing/Power input Voltage 220~480VAC Single Phase 50/60HZ
Frequency U/F Range 42~60HZ
Output Voltage Maximum 90VDC @ 220VAC
Current Continuous 6A Maximum 8A for 10 sec.
Voltage Regulation < ±1% (with 6% engine governing)

SR7 Introduction

Mecc Alte lists SR7/2-G as a legacy analogue AVR for several ECP frames.

Analogue board or digital retrofit?
Compare the original board suffix and its terminal markings. If sourcing a DSR or DER1 retrofit, request the alternator-specific wiring and configuration.

Global Market Price Reference (USD)

For the SR7-2G / SR7/2-G revision, market offers ranged from US$28.75 to US$406.00 per AVR. Low-priced replacements were plentiful, while a listing advertised as original Mecc Alte supply set the high endpoint. For alternator-service procurement, specify the exact SR7 revision and compare documented supply identity, terminals and accessory connections before negotiating a batch quote. This revision-specific reference excludes used boards, SR7 RT80A and other regulators merely advertised as substitutes.

How do I identify the correct regulator variant?

Use the alternator nameplate and the printed regulator reference together; similar enclosures can contain different electronics — confirm the specification with our team.

View this answer in FAQs ↗
Can I replace this regulator with a universal unit?

Universal replacement is possible only when excitation and sensing characteristics match. Confirm before ordering — confirm the specification with our team.

View this answer in FAQs ↗
Which alternators use Mecc Alte regulators?

They are applied to Mecc Alte alternators and compatible excitation systems. Specific pairing must be confirmed — confirm the specification with our team.

View this answer in FAQs ↗
Why does the generator voltage rise with load reduction?

Voltage rise on load removal can indicate regulator response settings or sensing problems. Review stability settings and confirm sensing wiring.

View this answer in FAQs ↗
What should I include when requesting a price?

Include the alternator model, regulator reference, rated output, excitation arrangement, quantity and installation photos. ---

View this answer in FAQs ↗